ADEMCO VISTA 10 Instrukcja Konfiguracji Strona 49

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 48
71
SECTION 7
Zone Lists
(
81 Menu Mode)
•••••••••••••••••••••••••••••••••••••••••••••••••
About Zone Lists
Zone lists let you group individual zones for use with certain system actions. This interactive menu mode is
used to program zone lists for output devices previously programmed in
80. Refer to the Programming
Form worksheet (
81) that programs the Zone Lists for Output Relays. The following table indicates the
available zone lists and their purpose.
Zone List No. Used for
01
Starting
or
stopping a relay action (enter 00 to end entries); general purpose
02
Starting
or
stopping a relay action (enter 00 to end entries); general purpose
03
Starting
or
stopping a relay action (enter 00 to end entries); general purpose
Zone List Programming
Zone List programming involves:
1.
Selecting an appropriate zone list number
2.
Adding the desired zone numbers to that list.
Start Zone List Programming mode by pressing
81 while in the Programming mode. The following prompts
are displayed.
81 Menu Mode
PROMPT VALID ENTRIES EXPLANATION
ZONE LIST NO.
(00 = Quit 01
Zone List Number
01 - 03 = zone list number
[
]
to continue
Enter the Zone List number
01
,
02
, or
03
you want to program (or
00
to end these entries).
In the following displays, zone list 01 has been selected for
programming.
01 Enter Zn Num.
(00 = Quit) 00
Zone Number
01
- 25
=
zone list number
00 to advance
Enter each zone number to add to the zone list by first entering
the zone number, then
(for example, 01
, 02
, 03
). After all
zones desired are entered, press
00
to advance.
IMPORTANT:
Do not include fire zones in zone lists that are used
to STOP relay actions.
01 Del Zn List?
0 = No 1 = Yes 0
Delete Zone List
0 = to advance
To delete the zone list, enter
1
(Yes). All zones in the zone list are
deleted automatically, and programming returns to the first screen.
01 Delete Zone?
0 = No 1 = Yes 0
Delete Zone
1 = to advance
To save the entire zone list, enter
0
(No). Programming returns
to the first screen.
To delete a zone or zones in a zone list, enter
1
(Yes) to advance.
01 Zn to Delete?
(00 = Quit) 00
Zone to Delete
00 = to return to first screen
Enter each zone to be deleted from the list, followed by
. After all
zones to be deleted are entered, enter
00
to return to the first
screen so that another list can be programmed, if desired.
Any list may include any or all of the system's zone numbers
except
zone 08.
A zone list can be assigned to more than one output relay.
Przeglądanie stron 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 79 80

Komentarze do niniejszej Instrukcji

Brak uwag