Section 4 - Data Field Programming
4-5
With ADEMCO Contact ID
®
Reporting:
Enter any digit (other than 0) in the
first
box, to enable zone to report This is
an "enabling" code only and is disregarded in the actual reporting to the central office. Entries in the
second
boxes will
be ignored.
A 0 (
not
# + 10) in the
first
box will disable the report.
Examples:
For Code
3
(single digit), enter:
3 0
For Code
32
(two digits), enter:
3 2
For Code
B2
(hexadecimal) enter
:
# + 11
2
FIELD TITLE and DATA ENTRIES EXPLANATION
SYSTEM STATUS REPORT CODES (
✱
60
–
✱
68)
✱
60
Trouble Report Code
0 = no report
For both digits: 1-9, A-F (Refer to above
table for method of programming report
codes.)
This is a 2-digit entry field.
This will be sent if a zone has a trouble condition.
✱
61
Bypass Report Code
0 = no report
For both digits: 1-9, A-F (Refer to above table
for method of programming report codes.)
This is a 2-digit entry field.
This will be sent when a zone is manually bypassed.
Refer to above table
for method of constructing 2-digit
codes.
✱
62
AC Loss Report Code
0 = no report
For both digits: 1-9, A-F (Refer to above table
for method of programming report codes.)
This is a 2-digit entry field.
Timing of this report is random with up to a 48 minute
delay. The AC RESTORE report has a random delay of
about 12 minutes. If AC restores before the report goes
out, there is no “AC RESTORE” report.
✱
63
LOW BAT Report Code
0 = no report
For both digits: 1-9, A-F (Refer to above table
for method of programming report codes.)
This is a 2-digit entry field.
This is sent when a low battery condition exists in the
system’s standby battery.
✱
64
TEST REPORT CODE
0 = no report
For both digits: 1-9, A-F (Refer to above table
for method of programming report codes.)
This is a 2-digit entry field.
This is sent periodically to test that the communicator and
phone lines are operational.
✱
65
Open/Exit Alarm Report Code
0 = no report
For both digits: 1-9, A-F (Refer to above table
for method of programming report codes.)
This is a 2-digit entry field.
This is sent periodically to test that the communicator and
phone lines are operational.
Open Report Code:
To enable, enter a code (or 0 to disable) in the left-hand box (see box above).
For expanded or 4+2 reporting,
2nd digit = User No.
Exit Alarm Report Code:
To enable, enter a code (or 0 to disable) in the right-hand box (see box above).
If enabled,
any alarm from an exit or interior zone occurring within two minutes after the end of
the exit delay
will send a special message indicating exit alarm to the central station, and a zone
indication and "Exit Alarm" or "EA" is displayed on the keypad.