Section 2 - Installing the Control & Peripherals
2-5
AC Powerup
To turn on AC power, perform the following steps:
1. Plug the 1321/1321CN into a 24-hour,
unswitched
120VAC outlet.
Following powerup, one of the following is displayed
on the keypad:
AC
,
dI
(disabled),
BUSY STANDBY
(on alpha keypads), or
NOT READY
(on fixed-word
keypads). The green POWER LED (or READY LED
on some keypads) should light.
2. After approximately 1 minute, the initial displays
revert to
DISARMED...READY TO ARM
for alpha
keypads, or
READY
for fixed-word keypads (if there
are no faulted zones). This 1-minute delay allows
PIRs, etc. to stabilize.
To bypass this delay, press:
#
+
0
.
NOTE
:
If you do not get the READY display
described above, refer to Trouble Conditions
paragraph in SECTION 10: System Operation.
Backup Battery
1. Place the 12-volt backup battery in the cabinet.
2.
After all connections to the control are completed,
connect the red and black flying leads on the
control board to the battery. Do
NOT
attach these
leads to the battery terminals until all connections
and wiring have been completed.
Notes:
Refer to the California State Fire Marshal and UL
Residential Fire requirements statement below, if
applicable.
U
L
Only use a 17.2AH battery for UL installations.
OUTPUT LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACKUP REQUIREMENTS
AND UL RESIDENTIAL FIRE INSTALLATIONS
OUTPUT CURRENT LIMITATIONS BATTERY INFORMATION
Output Current Total Maximum Auxiliary Current
Battery Capacity
To Use (Amp/Hrs)
Recommended Battery
(Yuasa Model No.)
600mA maximum total
of auxiliary power plus
bell output currents
45mA
160mA
200mA
425mA
500mA
4AH
7AH
8AH
14AH
17.2AH
NP4-12
NP7-12
NP4-12 (two)
NP4-12 (two)
NPG18-12
NOTE:
Use two batteries, connected in parallel. Obtain an ADEMCO Battery Harness Kit SA5140-1. (Both batteries will fit
inside the panels cabinet.)
AUXILIARY DEVICE CURRENT DRAIN WORKSHEET
DEVICE
CURRENT
# UNITS
TOTAL CURRENT
6128 Keypad 30mA
6139 Keypad 100mA
5881/5882 RF Receiver 35mA
4204 Relay Unit 15/180mA
4285 VIP Module 160mA
4286 VIP Module 300mA
*
TOTAL =
Current available from Aux. terminals = 500mA max
*
If you are using hardwire devices such as PIRs, refer to the specifications for that particular unit's current drain.
In UL installations, max current drain from the Auxiliary Output and the Alarm Output
combined
must not exceed 600mA.
Figures are for relays de-energized (OFF)/relays energized (ON).