VISTA-15/VISTA-15CN Installation and Setup Guide
15–6
Pager Report Format
Entries 6 through 9 sends a report to a pager, using the following format:
The Pager report is formatted as follows:
AAAAAAAAAAAAAAAA
–
BBB
–
CCCC
where:
A
= (Optional.) Up to 16 digits for account numbers, PIN numbers, or any
additional data that precedes the 7-digit system status code BBB and CCCC
(see
B
and
C
below). This optional data is programmed in field
✱
88, Paging
Characters.
B
= A 3-digit code that describes the event that has occurred in the system (see
the explanation below).
C
= A 4-digit user or zone number, depending on the type of event that has
occurred. For alarms or troubles, these digits represent the zone number. For
openings (disarming) and closings (arming), these digits represent the user
number. In this system, the first 2 digits are always “00.” Single-digit zone
or user numbers are also preceded by a “0.”
The 3-digit Event codes (BBB) that can be sent are:
911
=
Alarms
. The 4-digit number (CCCC) that follows this code is the zone
number that has caused the alarm.
811
=
Troubles
. The 4-digit number (CCCC) that follows this code is the zone
number that has caused the trouble.
101
=
Open
(system disarmed). The 4-digit number (CCCC) that follows this
code is the user number.
102
=
Close
(system armed). The 4-digit number (CCCC) that follows this code
is the user number.
✱
48 DIALER DELAY (BURG/FIRE) (in seconds)
1 | 0
0 = no dialer delay; 1 = 15; 2 = 30; 3 = 45; 4 = 60; 5 = 120 Burg Fire
Above options (1 through 5) 1 = provide 15-second delay of
BURGLARY ALARM
and
FIRE ALARM
reporting to the Central Station, which allows time for the
subscriber to avoid a false alarm transmission. This delay does
not
apply to zone
type 12 (24-Hour Monitor), zone type 24 (Silent Burglary), zone type 06 (24-Hr
Silent), zone type 07 (24-Hr Audible), and zone type 08 (24-Hr Aux) which are
always sent as soon as they occur.
UL installations: Must be set to 0 (no delay).
✱
49 PERIODIC TEST REPORT
0
0 = no test report
1 = once every 24 hours
2 = weekly
3 = once every 30 days
Test Report Code entered in field
✱
64 is sent. Reports with Subscriber No.
✱
50 TEST REPORT OFFSET
2
0 = 24 hours after exiting Program mode or download
1 = 6 hours after exiting Program mode or download
2 = 12 hours after exiting Program mode or download
3 = 18 hours after exiting Program mode or download
This is the time to first report from Programming mode or downloading.
✱
51 SESCOA/RADIONICS SELECT
0
0 = Radionics (0–9, B–F reporting)
1 = SESCOA (0–9 only reporting)
Select 0 for all other formats.