VISTA-15/VISTA-15CN Installation and Setup Guide
B-2
California State Fire Marshal (CSFM) 24-Hour Battery Back-Up Requirements
The California State Fire Marshal has published new regulations which require that all
residential fire alarm control panels installed after June 30, 1993 must be provided with a
back-up battery which has sufficient capacity to operate the panel and its attached
peripheral devices for 24 hours in the intended standby condition, followed by at least 4
minutes in the intended fire alarm signaling condition.
This control panel can meet these requirements without using a supplementary power
supply, provided that the panel's auxiliary power and bell output currents are limited as
indicated in the following table.
OUTPUT LIMITATIONS TO MEET CSFM 24-HOUR BATTERY BACK-UP REQUIREMENTS
FOR UL LISTED RESIDENTIAL FIRE INSTALLATIONS
OUTPUT CURRENT LIMITATIONS BATTERY INFORMATION
OUTPUT CURRENT
TOTAL
MAXIMUM
AUXILIARY CURRENT
BATTERY CAPACITY
TO USE (Amp/Hrs)
RECOMMENDED BATTERY
(Yuasa Model No.)
600mA maximum total
of
auxiliary power
plus bell output
currents.
45mA
160mA
200mA
425mA
4AH
7AH
8AH
14AH
NP4-12
NP7-12
NP4-12 (two)
NP7-12 (two)
Note: Use two batteries, connected in parallel. Obtain an ADEMCO No. 4100EOLR Resistor Kit. A dual battery
harness is provided with the kit. The kit also contains EOL resistors with spade lug/heat shrink tubing
construction which has been approved by UL and CSFM for fire zone usage. Both batteries will fit inside
the panel's cabinet.