VISTA-128B Installation Instructions
6-4
4-WIRE
SMOKE
DETECTOR
EOL
RELAY
NO CONNECTION
{
TO
PANEL
ZONE
(ZONE 2-8)
{
TO
PANEL
AUXILIARY
POWER
(TERMINALS 6, 7)
CNCNO
RESET
RELAY 1, 2, 3 OR 4
4204 RELAY MODULE
NOTES:
• PROGRAM THE RELAY TO
TRANSFER ON FIRE ZONE
RESET (ACTIVATION CODE 54).
SEE 4204 RELAY MODULE
SECTION FOR DETAILS.
• SECOND CODE AND OFF
ENTERED AT CONSOLE
MOMENTARILY INTERRUPTS
DETECTOR POWER.
+
+
+
+
Figure 6-3: 4-Wire Smoke Detector Connections (Zones 1-8)
1. Connect detectors (including heat detectors, if used) across terminals of the zone selected.
All detectors must be wired in parallel. Remove the 2000-ohm EOL resistor if connected
across the selected zone terminals. You must connect the EOL resistor across the
loop wires at the last detector.
Compatible 4-Wire Smoke Detectors
Use any UL Listed 4-wire smoke detector which is rated for 10-14VDC operation and which
has alarm reset time not exceeding 6 seconds. Some compatible 4-wire smoke detectors are
listed below.
Photoelectric, direct wire System Sensor 2412
Photoelectric w/heat sensor, direct wire System Sensor 2412TH
Ionization, direct wire System Sensor 1412
Wiring 2-Wire Latching Glassbreak Detectors to Zone 8
Use zone 8 for connection of compatible 2-wire latching-type glassbreak detectors. Wire as
follows:
1. Connect all detectors in parallel across zone 8 (terminals 21 and 22). See Figure 6-4.
Remove the 2000-ohm EOL resistor if connected across the selected zone terminals. You must
connect the EOL resistor across the loop wires at the last detector.