Section 6 – Basic Hardwired Zones
6-3
2k EOLR
ZONE 1
SMOKE
(+)
(-)
2-WIRE SMOKE
DETECTOR
10
11
(+)
(-)
Figure 6-2: 2-Wire Smoke Detector Connected to Zone 1.
Compatible 2-Wire Smoke Detectors
You may use up to 16 2-wire smoke detectors on zone 1 listed in the table below.
DETECTOR TYPE DEVICE MODEL # DETECTOR TYPE DEVICE MODEL #
Photoelectric, direct wire System Sensor 2400 Photoelectric duct detect.
w/DH400 base
System Sensor 2451
Photoelectric w/heat
sensor, direct wire
System Sensor
2400TH
Ionization duct detector
w/DH400 base
System Sensor
1451DH
Photoelectric w/B401B
base
System Sensor 2451 Ionization, direct wire System Sensor 1100
Photoelectric w/heat
sensor and B401B base
System Sensor
2451TH
Ionization w/B110LP base System Sensor 1151
Ionization, direct wire System Sensor 1400 Photoelectric, direct wire System Sensor 2100
Ionization w/B401B base System Sensor 1451 Photoelectric w/heat sensor,
direct wire
System Sensor 2100T
Photoelectric duct detect.
w/DH400 base
System Sensor 2451 Photoelectric w/B110LP base System Sensor 2151
U
L
These smoke detectors are UL Listed for use with the VISTA-128B and are the
only
2-wire
smoke detectors that may be used.
Wiring 4-Wire Smoke Detectors to Zones 1-8
When programmed for fire warning usage, zones 1-8 can monitor 4-wire smoke detectors,
N.O. fire alarm initiating devices, or N.O. sprinkler system supervisory devices.
You may use as many 4-wire smoke detectors as can be powered from the panel's Auxiliary
Power output without exceeding the output's rating (see the Final Power-Up Procedure
section for auxiliary power ratings).
Auxiliary power to 4-wire smoke detectors is not automatically reset after an alarm, and therefore
must be momentarily interrupted using either an external switch or a 4204 Relay Module.
U
L
Power to 4-wire smoke detectors must be supervised with an EOL device (use a System Sensor
A77-716B EOL relay module connected as shown in
Figure 6-3
).