Section 23 - #93 Menu Mode Programming
23-11
010 INPUT S/N
A 022-4064
Serial #
The system will enroll the first serial number heard, display
the serial numbers, and cause the keypad to beep twice.
If the serial and loop number combination is already present in the system, the keypad will sound a
single long beep and display the word "DUPLICATE" along with the serial number, and the number
of the zone containing the serial/loop number combination.
The system will then enter an optional confirmation mode so that the operation of the actual
programmed input can be confirmed. Activate the loop input or button that corresponds to
this zone.
We recommend that you confirm the programming of every device before
proceeding to the next zone.
010 CONFIRMED SL:1
A022-4064
When the system sees activity on the appropriate input, it will
beep three times and display the confirmation message. Press
[
]
or the upper left-hand button of the program tool when you
are ready to enroll the next serial number device.
At any time during this step, you may press
[
]
on the keypad or the upper left-hand button of the
program tool if you are satisfied with the serial and loop number combination that has been
enrolled, regardless of whether or not the enrolled input has been "confirmed." This will ready the
system to enroll the next serial number device.
If the incorrect device has been enrolled, press [#] on the keypad or the upper right-hand button of
the program tool to delete the serial number and return to the "LEARN S/N?" prompt. A single long
beep will be heard from the keypad to verify pressing of the upper right-hand button. Then, press
1
(Yes) or press the upper left-hand button of the program tool (a single short beep will verify the
system is ready for enrolling) and re-activate the proper device or device loop input.
The system will search for the next zone that does not have a serial number associated with
it. If one is found, the system will return to the “INPUT S/N” prompt for the remaining
zones.
After all zones have been displayed, whether enrolled or not, the "ENTER ZN NO." prompt
will appear. Enter
000
to exit the Sequential Mode and return to Data Field Programming
Mode.
When you have finished programming all zones, test each using the system's Test Mode. Do not
use the Transmitter ID Sniffer Mode for this, as it will only check for transmission of one zone on a
particular transmitter, NOT the zones assigned to each additional loop, and will NOT verify polling
loop type.