ADEMCO 4120XM Podręcznik Użytkownika Strona 68

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 80
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 67
4120XM CONTROL
Physical: 12-1/2”W X 14-1/2”H X 3“D
(317mm x
368mm x 76mm)
Electrical:
Voltage Input: From Ademco No. 1321/TF2 Plug-In Transformer
(use 1321CN in Canada) rated 16.5VAC, 25 VA.
A/arm Sounder Otput: 10VDC-13.8VDC, 2.8 amps max. (non-UL
installations). See UL note below.
Aux.Power Output:9.6VDC-13.8VDC, 700mA max (700 mA less
Aux current draw for UL installations). For UL installations, the
accessories connected to the output must be UL Listed, and rated
to operate in the above voltage range.
UL NOTE: The current draw from the Aux Output and Alarm
Output combined must not exceed 700 mA in UL installations.
Back-up Battery: 12VDC, 4AH or 7AH gel cell. YUASA NP4-12
(12V, 4AH) or NP7-12 (12V, 7AH) recommended. Use 4AH
battery for UL installations.
Standby: 4 hours min. with 500 mA aux. load using 4AH battery.
Circuit Protectors: Thermal circuit breakers are used on battery
input to protect against reverse battery connections and on alarm
sounder output to protect against wiring faults (shorts) and on
auxiliary power output to protect against wiring faults (shorts).
DIGITAL COMMUNICATOR
Formats Suppoded:
ADEMCO HIGH SPEED
ADEMCO 4+2 EXPRESS
ADEMCO LOW SPEED
ADEMCO CONTACT ID
SESCOA
RADIONICS LOW SPEED
LINE SEIZE: Double
Pole
RINGER EQUIVALENCE: 0.7B
FCC REGISTRATION NO.: AC398U-681 92-AL-E
4127
REMOTE CONSOLE
Physical: 5-5/8”W X 4-1 1/16“H
X 7/8”D
(143mm x119mm
x 22mm)
Electrical:
Voltage Input: 12VDC
Current Drain: 20 mA
Interface Wiring:
RED:
12VDC input (+) - auxiliary power
GREEN: Data to control panel
YELLOW: Data from control panel
BLACK: Ground and (-) connection from supplemental
power supply.
4137AD15137AD REMOTE
Physical: 8.4” W
X 4.75” H X 1.1” D
CONSOLES
(213mm x 121mm x 28mm)
Electrical: Voltage Input: 12VDC
Current Drain: 60
mA (4137AD)
90 mA (5137AD)
Interface Wiring:
RED:
12VDC
input (+) auxiliary power
BLUE:
(If present) Not Used
GREEN: Data to control panel
YELLOW: Data from control panel
BLACK: Ground and (-) connection from supplemental
power supply.
-ss -
Przeglądanie stron 67
1 2 ... 63 64 65 66 67 68 69 70 71 72 73 ... 79 80

Komentarze do niniejszej Instrukcji

Brak uwag