ADEMCO LYNXR Series
Security Systems
LYNXR/LYNXR24 and LYNXR-EN
Installation and Setup Guide
AWAY
OFF
STAY
AUX
4
5
6
7
8
9
0
#
1
2
3
K5963V3bx 5/04 Rev. A
Przeglądanie stron 0
1 2 3 4 5 6 ... 71 72

Podsumowanie treści

Strona 1 - Security Systems

ADEMCO LYNXR Series Security Systems LYNXR/LYNXR24 and LYNXR-EN Installation and Setup Guide AWAYOFFSTAYAUX4567890#123

Strona 2 - BEDROOMBEDROOM

–10– AC Power and Backup Battery AC Power and Rechargeable Backup Battery The LYNXR Series is equipped with an integral, replaceable, rechargeable ba

Strona 3 - Table of Contents

–11– Installing Wireless Zones General Information Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16

Strona 4 - System Features

–12– Installing Wireless Zones Transmitter Battery Life • Batteries in the wireless transmitters may last from 4–7 years, depending on the environ

Strona 5 - Mounting the Control

–13– Installing Wireless Zones 5800 Series Transmitter Loop Numbers (Refer to this information when programming transmitters) The following illustra

Strona 6 - Wiring Connections

–14– Mechanics of Programming General Programming Information Programming options are stored in non-removable, electrically erasable, nonvolatile

Strona 7

–15– Zone Response Type Definitions General Information During programming, you must assign a zone type to each zone, which defines the way in which

Strona 8

–16– Zone Response Type Definitions Type 07 24-hour Audible Alarm Zone type 07 is usually assigned to a zone containing an Emergency button (audib

Strona 9

–17– Data Field Descriptions Defaults (where applicable) are Indicated in Text. The following pages list all data fields in this Control (in numeric

Strona 10 - AC Power and Backup Battery

–18– Data Field Descriptions ✻35 Entry Delay 01 00-99 = entry delay time in seconds. The system will wait the time entered before sounding alarm up

Strona 11 - Installing Wireless Zones

–19– Data Field Descriptions Field 46: Enter up to 24 digits. Do not fill unused spaces. Enter 0-9, #+11 for ‘*’; #+12 for’#’; #+13 for a pause (2 s

Strona 12 - 01009-011-V0

–2– RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper

Strona 13 - 01000-013-VO

–20– Data Field Descriptions ✻50 15-Second Dialer Delay (Burglary) 0 = no dialer delay 1 = provide 15-second delay of burglary alarm report when arm

Strona 14 - Mechanics of Programming

–21– Data Field Descriptions SYSTEM STATUS REPORT CODES (✻59–✻68) ✻59 Exit Error Report Code (See notes above) If the system is armed and an entry

Strona 15 - 01000-018-V0

–22– Data Field Descriptions RESTORE REPORT CODES (✻70–✻76) Continued ✻75 RF Transmitter Low Batt. Restore Code (See notes above) Sent when a tran

Strona 16 - 01000-020-V0

–23– Data Field Descriptions ! The features programmed in Field ✻91 differ between LYNXR models. Ensure you use the correct option for the model you

Strona 17 - Data Field Descriptions

–24– Data Field Descriptions Other Programming Commands ✻55 ENABLING THE WIRELESS DIALER Interactive menu mode used for enabling the 5842 Wireles

Strona 18

–25– ✻55 Enabling the 5842 Wireless Dialer This is an interactive menu mode that is used to enable and program the 5842 Wireless Dialer. When enable

Strona 19

–26– ✻55 Enabling the 5842 Wireless Dialer While in Program mode, press ✻55 to enter Wireless Dialer Programming Feature. The following explains th

Strona 20

–27– ✻56 Enhanced Zone Programming Mode This is an interactive menu mode that is used to program zone numbers, zone types, alarm and report codes, a

Strona 21

–28– ✻56 Enhanced Zone Programming Mode While in Program mode, press ✻56 to enter Zone Programming Menu Mode. Refer to the zone assignment table for

Strona 22

–29– ✻56 Enhanced Zone Programming Mode RF Learning - Two (2) transmissions (2 key depressions) at least 5 seconds apart will be required for BR

Strona 23

–3– Table of Contents SYSTEM FEATURES ...

Strona 24

–30– ✻56 Enhanced Zone Programming Mode Manual entry Enter "1" to advance to Serial number prompt (1b). Copy the previous serial number

Strona 25 - ✻55 are as follows:

–31– ✻80 Device Programming Menu Mode Powerline Carrier devices (eg., X-10 brand devices) are programmable switches that can be used to perform many

Strona 26 - Enable back-up reporting

–32– ✻80 Device Programming Menu Mode STOP The "STOP" programming determines when and under what conditions the device will be de-activate

Strona 27 - ✻56 are as follows:

–33– ✻80 Device Programming Menu Mode The following explains these prompts in detail. The left two columns identify the prompts and list the availab

Strona 28

–34– ✻81 Zone List Menu Mode While in Program mode, press ✻81 to enter Zone List Menu Mode. This mode is used to program zone lists for output devic

Strona 29 - IA LC

–35– ✻83 Enhanced Sequential Mode By using this mode, you can add, delete, or change the serial number of a transmitter in a zone, but retain all ot

Strona 30 - IF vi

–36– ✻83 Enhanced Sequential Mode IA zz IA LC Enroll mode 0 = advance to next zone to be enrolled 1 = enter now and proceed to SERIAL N

Strona 31 - Programming Options Defined

–37– ✻83 Enhanced Sequential Mode Ib zz Ib Serial number Enter transmitter’s 7- digit serial number via RF learning or manually. [#] = return

Strona 32 - ✻80 are as follows:

–38– ✻84 Assign Zone Voice Descriptors Use this mode to assign voice descriptors for each zone. These are the descriptors that are announced when th

Strona 33

–39– ✻84 Assign Zone Voice Descriptor VOICE VOCABULARY INDEX 00 ½ second pause A 82 ALARM 32 ATTIC B 01 BABY 33 BACK 34 BASEMENT 35 BATHRO

Strona 34 - 81 Zone List Menu Mode

–4– System Features UUUULLLL LYNXR and LYNXR-EN are not intended for UL985 Household Fire applications unless a 24-hour backup battery (P/N LYNXR

Strona 35 - 83 Enhanced Sequential Mode

–40– ✻85 Record Custom Voice Descriptors Use this mode to record up to 5 custom voice descriptors. Press ✻85 while in Programming mode. Note: Enteri

Strona 36

–41– Voice Prompt Programming The LYNXR Series features a quick programming mode that allows you to program the system by responding to a series of

Strona 37

–42– Voice Prompt Programming Enter Voice Prompt Programming Mode: (Installer Code + 8 8 8). Follow the voice prompts to advance to the selected item

Strona 38 - Descriptor 3

–43– Voice Prompt Programming To Delete Sensors To Add an Emergency Pendant (5) Pendant Type Medical Fire Silent Police Police ! When adding wir

Strona 39 - VOICE VOCABULARY INDEX

–44– Voice Prompt Programming ! All four digits of the Central Station Account number must be entered. If ten-digit format is selected, all ten digi

Strona 40 - Custom descriptor number

–45– Remote Programming/Control (Downloading) General Information The control panel can be remotely programmed from an IBM-compatible Personal Comput

Strona 41 - Voice Prompt Programming

–46– Remote Programming/Control (Downloading) • Command the system to upload a copy of its resident program to the office. • Set the time • View/Mo

Strona 42

–47– System Operation Security Codes Installer Code The installer programs the 4-digit Installer Code initially as part of the programming procedur

Strona 43

–48– System Operation Keypad Functions The keypad allows the user to arm and disarm the system, and perform other system functions, such as bypassi

Strona 44

–49– System Operation Speaker Phone Operation (LYNXR-EN Only) To place a call or answer a call using the speaker phone: [#] + AUX To flash (sw

Strona 45 - (Downloading)

–5– Mounting the Control Wall Mounting The illustration below shows the front assembly separated from the back plate. ! DO NOT disconnect the ribb

Strona 46 - Windows

–50– System Operation UUUULLLL Alarm audio verification cannot be used for UL installations. Alarm Audio Verification (Two-Way Voice Feature)

Strona 47 - System Operation

–51– System Operation “Follow Me” Reminder Feature This feature allows the user to schedule a time driven message. When activated the system will

Strona 48

–52– System Operation Trouble Conditions The word “FAULT” on the keypad’s display, accompanied by a rapid “beeping” at the keypad, indicates that

Strona 49

–53– Testing the System Test ModeAfter installation is completed, the security system should be carefully tested, as follows. 1. With the system

Strona 50

–54– System Communication This section provides an explanation of formats this system accommodates for reporting alarms and other system conditio

Strona 51

–55– System Communication Report 3+1/4+1 Standard 3+1/4+1 Expanded 4+2 Alarm SSS(S) A SSS(S) A AAA(A) Z SSSS AZ Trouble SSS(S) T SSS(S

Strona 52

–56– Troubleshooting Guide SYSTEM (including Wireless) SYMPTOM POSSIBLE CAUSE REMEDY 1. Transmitter signal not received at control. 1a. Transmi

Strona 53 - Testing the System

–57– Troubleshooting Guide CONTROL SYMPTOM POSSIBLE CAUSE REMEDY 1. The word “AC” is not displayed. 1a. Interrupted AC power supply. 1a. Chec

Strona 54 - System Communication

–58– Contacting Technical Support PLEASE, before you call Technical Support, be sure you: • READ THE INSTRUCTIONS! • Check all wiring connection

Strona 55

–59– Regulatory Agency Statements UL NOTICE: This is a "Grade A" residential system. FCC ID: CFS8DLLYNXREN-2 CANADA: 1748A-LYNXREN2 FCC S

Strona 56 - Troubleshooting Guide

–6– Wiring Connections Wiring Overview The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary

Strona 57

–60– Specifications LYNXR-Series Security Controls 1. Physical: 10-3/8” W x 7-1/8” H x 1-3/4” D 2. Electrical: VOLTAGE INPUT: 9VAC from plug

Strona 58 - Contacting Technical Support

– 61 – LYNXR/LYNXR24 PROGRAMMING DEFAULT TABLES (boldface indicates defaults that differ between tables) Function Table 1 Table 2 Table 3 Table

Strona 59 - Regulatory Agency Statements

– 62 – LYNXR-EN PROGRAMMING DEFAULT TABLES (boldface indicates defaults that differ between tables) Function Table 1 Table 2 Table 3 Table 4 *20

Strona 60 - Specifications

– 63 – ✻56 ZONE ASSIGNMENT/ALARM REPORT CODES FOR TABLE 1 Zone No. Zone Type Alarm Code Input Type Loop Number Zone Descriptor 1 0 0,0 --- -

Strona 61 - 2 2 2 2

– 64 – ✻80 DEFAULT TABLE: APPLIES TO DEFAULT TABLE 4 (devices 2-7 have no default values) Start Stop Device Number Action Event Zone List Z

Strona 62 - 2 2 2 2

– 65 – –Index – *55 Enabling the 5842 Wireless Dialer ... 25 *56 Enhanced Zone Programming Mode...11, 2

Strona 63

– 66 – E EA ... 51 Earth Ground...

Strona 64 - 8** 2 33 36

– 67 – Remote Programming... 45 Remote Programming/Control...

Strona 65 - –Index –

– 68 – -Notes-

Strona 66

– 69 – WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protectio

Strona 67

–7– Wiring Connections Wiring Connections 2. Make Phone Line Connections - For local or full line seizure proceed to the appropriate steps below.

Strona 68 - -Notes

– 70 – LIMITED WARRANTY Honeywell International Inc. acting through its Security & Custom Electronics business ("Seller"), 165 Eileen W

Strona 69 - WARNING

– 71 – INCOMINGPHONELINETO HANDSETPHONELINEWARNING:TO PREVENTRISK OFSHOCKDISCONNECTTELEPHONELINE AT TELECOMJACK BEFORESERVICINGTHIS UNIT.WEEKLY TESTI

Strona 70

‡K5963V3oŠ K5963V3bx 5/04 Rev. A 165 Eileen Way, Syoss

Strona 71 - TRIGGER SIGNAL (NEG)

–8– Wiring Connections INCOMINGPHONELINETOHANDSETPHONELINEWARNING:TO PREVENT RISK OF SHOCKDISCONNECT TELEPHONE LINEAT TELECOM JACK BEFORESERVICING

Strona 72 - ‡K5963V3oŠ

–9– AC Power and Backup Battery The system is powered by a 9VAC, 15VA Plug-in Transformer, ADEMCO 1332/1332X10 (1332CN in Canada). Refer to the wir