Zone 1
(Cent)
Zone 1 Advisories
Zones 2-8
EOLR Fire Zone:
●
●
●
●
●
●
●
●
●
Program Zone 1 as a Fire zone (type 09).
Program Field
●41 as a “O” (EOLR required).
Leave Red PCB jumper intact.
Supports up to eight (8) 2-wire smoke detectors.
Open circuit devices must be connected in parallel
across terminals 9 & 10. A
2000 ohm EOLR must be
connected across the furthest device.
Connect closed circuit devices in series with the loop.
Field 1*46 (AUX Output Enable) may be set to “3”
(zone 1 EOLR)
Second OFF sequence momentarily interrupts the
loop power to reset the smoke detectors.
See table below for compatible smoke detectors.
Compatible Smoke Detectors
Detector Type Device Model #
Photoelectric w/heat sensor, direct wire.............. System Sensor 2300T
Photoelectric, direct wire
..................................... System Sensor 2400
Photoelectric w/heat sensor, direct wire.............. System Sensor 2400TH
Photoelectric w/B401B base ................................System Sensor 2451
Photoelect. w/heat sensor& B401Base. ...........
System Sensor 2451TH
Ionization, direct wire .......................................... System Sensor 1400
Ionization w/B401B base
.....................................System Sensor 1451
Photoelectric duct detector w/DH400 base.........
System Sensor 2451
Ionization duct detect. w/DH400 base ................ Svstem Sensor 1451DH
If the EOLR is not at the end of the loop, the zone is not properly supervised. The
system may not respond to an open circuit within the zone.
The alarm current provided by this zone is sufficient to support operation of only
one detector in the alarmed state.
UL NOTE: EOLRSare required for UL installations
The Following Table Summarizes Zones 2-8 Characteristics.
Applications
1Can be used for EOLR supervised or closed circuit
unsupervised devices. Can also support 4-wire smoke
detectors. Zone 8 can support latching glass break
detectors.
Zone Response Type Any.
Response Time Zones 1-7:350 msec; Zone 8: optional 10-15 msec
(as programed (field ●14)
Max. Zone Resistance s Zones 2, 3, 4, 5, 7, 8:300 ohms, excluding EOLR.
Zone 6:100
ohms.
Unsupewised Usage
. EOLR disabled in field
*41 (enter 1).
● Only closed circuit devices can be used.
EOLR Supervised
.
EOLR enabled in field ●41 (enter O).
● Supports both open circuit and closed circuit devices.
● Connect open circuit devices in parallel across the
loop. The 2,000 ohm EOLR must be connected
across the loop wires
at the last device.
● Connect closed circuit devices in series with the loop.
Glass Break Devices
● Supports up to 50 2-wire latching type glass break
on Zone 6
detectors.
● Configure as EOLR zone.
● Second CODE + OFF sequence momentarily
interrupts power to reset the glass break detectors.
“ See table that follows for compatible detectors.
(Continued over)
-11-