
Type 06
24-hour Silent Alarm.
Type 07
24-hour Audible Alarm.
Type 08
24-hour Auxiliary Alarm.
Type 09
Supervised Fire. (No
Verification)
Type 10
Interior w/Delay.
This zone type sends a report to the Central Station but provides no console
display or sounding. This zone type is usually assigned to a zone containing an
Emergency button.
This zone type sends a report to the Central Station, and provides an alarm
sound at the console, and an audible external alarm. This zone type is usually
assigned to a zone that has an Emergency button.
This zone type sends a report to Central Station and provides an alarm sound at
the console. (No
bell output is provided). This zone type is usually assigned to
a zone containing a button for use in personal emergencies, or to a zone
containing monitoring devices such as water sensors, temperature sensors, etc.
This zone type provides a fire alarm on short circuit and a trouble condition on
open circuit. The bell output will pulse when this zone type is faulted. This zone
type is always active and cannot be bypassed.
This zone type can be assigned
to any wired zone, but only certain wireless systems zones.
This zone type gives entry delay (using the programmed entry time), if tripped
when the panel is armed in the Away mode. This zone type is also active during
maximum mode, but no delay is provided (alarms occur immediately if zone is
tripped).
This zone type is bypassed when the panel is armed in the Stay or
Instant modes.
Delav beains whenever sensors in this zone are violated,
regardless of whether o; not;n entry/exit delay zone was tripped first.
IMPORTANT! FAULT ANNUNCIATION
RF faults (zones 88–91) will report as trouble conditions only, and as such,
should be assigned either zone type 00 if no annunciation is desired, or zone
type 05 if annunciation as trouble condition is desired. See
“Receiver Fault
Annunciation”
paragraph in WIRELESS ZONE EXPANS/ON section for more
information.
BASIC 8 HARD-WIRED ZONES
Zone 1
The Following Table Summarizes Zone 1 Characteristics.
Applications:
Zone Resnonse TvDe:
Response Time:
Max. Zone Resistance
Unsupervised Usage:
EOLR Supervised:
Can be used for EOLR supervised or closed circuit
unsupewised devices. It is the only zone that supports
2-wire smoke detectors.
Any
350 msec
100 ohms, excluding EOLR
●
●
●
●
●
Zone 1 should not be programmed as a fire zone.
Program Field *41 as a”1” (normally closed loops).
Cut Red PCB jumper.
Closed circuit burglary devices must be connected in
series with one another, with the series circuit
starting at terminal 10 and returning to terminal 12.
No EOLR is used across zone 1.
Field 1*46 (AUX Output Enable) may be set to “O”
(Ground Sta~) or”1” (Open/Close Trigger).
. Program Field
●41 as a “O”(EOLR required).
● Leave Red PCB jumper intact.
● Open circuit burglary devices must be connected in
parallel across terminals 9 and 10. A 2,000 ohm
EOLR must be connected across
the furthest
device.
c
Open circuit devices must be connected in parallel
across terminals 9 and 10. A 2,000 ohm EOLR must
be connected across
the fufihest device.
~
Field 1*46 (AUX Output Enable) must be set to “3
(zone 1 EOLR).
-1o-
Komentarze do niniejszej Instrukcji