5800 Series Transmitters Loop Designations
PROMPT
EXPLANATION
XMIT TO CONFIRM
PRESS TO SKIP
Confirmation Option: This prompt only appears if you answered “Yes” at the first prompt. The system
enters a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate
the loop input or button that corresponds to this zone. At any time during this step, you may press the [] key
on the keypad to save the serial and loop number combination without confirming.
Entd A022-4063 1
Rcvd A022-4064
If the serial number transmitted does not match the serial number entered, a display similar to the one
at the left appears. If the loop number does not match, it is also displayed.
If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary
display does not appear), press the [#] key twice and then enter or transmit the correct serial number.
010 ZT P RC In L
03 1 3C RF 1s
If the serial number transmitted does match the serial number entered, the system beeps 3 times and a
summary display appears, showing that zone’s programming. Note that an “s” indicates that a transmitter’s
serial number has been enrolled.
Press [] to accept the zone information.
ENTER ZONE NO.
000 = QUIT 011
The system now returns to the “ENTER ZONE NO.” prompt for the next zone.
When all zones have been programmed, enter “000” to quit.
After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in
the appropriate column on the worksheets provided later in this
Programming Guide
; then enter the other information
(zone number, zone type, etc.) relevant to that device.
When you have finished programming all zones, test each using the system's Test Mode. Do not use the
Transmitter ID Sniffer Mode. The system checks only for transmission of one zone on a particular
transmitter, NOT the zones assigned to each additional loop, and also does not verify polling loop type
zones.