
– 19 –
PROMPT
EXPLANATION
010 Silent ?
1 = YES 0 = NO 1
If you selected response type 1, 2, 3, 4, 5, or 10, this prompt will appear. Enter 1 to enable. The zone
follows all the selected response type’s characteristics, except in the alarm condition, the alarm output and
the keypad sounder do not sound and the keypad does not display the alarm condition.
Enter 0 to disable.
Press [✱] to continue.
010 Bypass Group
01-15 01
If you selected response type 1, 2, 3, 4, 5, or 10, this prompt will appear. Enter the bypass group for the
zone (01–15). This enables the user to bypass a group of zones by entering [User Code] + [6] (Bypass) +
[✱] + [Group No.] (01-15).
Enter 00 for None.
Press [✱] to continue.
010 Partition
1
Enter the partition number (1–8) you are assigning this zone to.
Press [✱] to continue.
010 REPORT CODE
1st 03 2nd 12 3C
Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting of 2
numerical digits. For example, for a report code of "3C," enter 03 for "3" and 12 for "C."
(Refer to the
System Communication
section in the
Installation and Setup Guide
for more information about
report codes and reporting formats.)
Press [✱] to continue.
010 BELL/RLY SEL
0
Each zone can be assigned to activate either one or both Notification Appliance Circuits and/or the system’s
auxiliary relay. Enter one of the following assignments:
0=none; 1=bell 1; 2=bell 2; 3=bell 1 & bell 2; 4=aux relay; 5=bell 1 & aux relay; 6=bell 2 & aux relay; 7=bell 1
& bell 2 & aux relay.
Press [✱] to continue.
010 INPUT TYPE
RF Xmitter 3
Input types 4 & 5 are
valid for certain 5800
Series transmitters only
If using input type 02
with a door/window type
transmitter, only loop 1
may be used.
Enter the input device type as follows:
00 = not used
01 = hardwired
02 = RF motion (RM type)
03 = supervised RF transmitter (RF type)
04 = unsupervised RF transmitter (UR type)
05 = RF button-type transmitter (BR type)
06 = serial number polling loop device (SL type)
07 = DIP switch-type polling loop device
08 = right loop of DIP switch type device
09 = keypad input (code + #73)
Right loops refer to the use of the right loop on a 4190WH Zone Expander Module and/or 4278EX PIR,
which allow hardwired devices to be monitored by the polling loop.
If you are programming hardwired or DIP switch polling loop devices, the summary display appears after
completing this entry.
NOTE: After programming, refer to the Installation and Setup Guide test section for testing of the RF
devices.
Press [✱] to continue.
010 SMART CONTACT
1 = YES 0 = NO
If input type 3 or 6 was selected, this prompt will be displayed. Enter 1 for devices that monitor maintenance
signals (ex. 5193SD, 5193SDT) or can be used to limit fault signals in the disarmed state (ex. Quest
2260SN). Otherwise, enter 0.
NOTES:
1. The Smart Contact option must ONLY be selected for devices that support the feature, otherwise
unpredictable results may occur.
2. if using the new 5193SD/SDT V-Plex smoke detectors (or older 5192SD/SDT with the maintenance DIP
sw enabled) the "Smart" option must be selected in zone programming or
when they enroll unpredictable
results may occur if the smoke goes into a High Sens or Low Sens condition.
001 Tamper Option
none 0
If you selected input type 1, 6, 7, or 8, this prompt displays. If the zone has a tamper switch wired in the
loop in addition to a sensor contact, enter the tamper option.
Enter 1 if the tamper switch is normally closed (wired in series) with the EOL resistor.
Enter 2 if the tamper switch is normally open (wired in parallel) with the EOL resistor.
Enter 0 if a tamper switch is not being used in the loop.
NOTE: For zone response types 9 or 16 (Fire), the tamper selection must be “0” none.
Komentarze do niniejszej Instrukcji