112
SPECIAL VL
REQVHREMENTS
UL 1023 HOUSEHOLD BURGLARY INSTALLATIONS
NOTE: CAN USE THE 4140XM. 4130XM. 5130XM OR 4140ATX.
INSTALLATION NOTES
1.
414OXM1414OATX max. altowabte current draw = 400 mA!UL
ALU. Power
- 300
mA siren
2. 4130XMI5130XM max. altowable current draw =
200
mAKiL
Aux. Power
= 100 mAsiren
3. (‘09) Entry delay #l/r1 1) Entry delay #2 cannot exceed 45 seconds.
4. (‘10) Exit delay #2/(‘12) Extt delay #2 cannot exceed 60 seconds.
5. (Y3) Atarm sounder duration cannot be less than 4 minutes.
6. C41) Use of End-of-Line resistors are mandatory for all UL installations.
7. (1’26) RF transmitter tow battery annunciation mrst be enabled.
6. (1’30) 4260 supervisory check-in monitoring interval cannot exceed 12
hOUts.
9. (1’31) RF transmitter check-in interval cannot exceed 12 hours.
10. (1.49) Audible sounder for transmitter check-in failure must be enabled.
11. (‘26) Power up in previous state must be enabled.
12. r23) Multiple Alamrs must be enabled.
13. (‘62) Disable Swinger Suppression: enter PO’.
UL 985 HOUSEHOLD FIRE INSTALLATIONS
NOTE: CAN USE THE 4140XM 413OXM. 5130XM OR 4146ATX.
INSTALLATION NOTES 1. (‘21) Fire timeout must be disabled (no fire timeout allowed).
2. (1’26) RF transmitter tow battery annunciation must be enabled.
3. (1’30) 4260 supervisory check-in monitoring interval cannot exceed 12
hours.
4. (1.31) RF transmitter check-in interval cannot exceed 12 hours.
5. (1’49) Audible sounder for transmitter check-in failure must be enabled.
6. (‘41) Use of End-of-Line resistors is mandatory for all UL installations.
,-.