110 SPECIAL VL REQUIREMENTS
UL 1610 GRADE AA CENTRAL STATION MERCANTILE BURGLARY
INSTALLATIONS USING HIGH LINE SECURITY DIRECT WIRE.
TRANSMISSION
IMPORTANT!: Requires the use of No. 4140ATX Control.
BELL CONNECTIONS
Audible alarms must be provided by the use of AB12 Bell in Box..The AB12
must be mounted so that it can be heard outside the protected area.
INSTALLATION NOTES
1. All wiring between AB12 and 4140ATX must be in conduit, and all
conduit holes (knackouts) on the Control panel shall be used or blocked
from access. (Bee Diagram 36.)
2. Use 12V 4 AH (minimum) Battery.
3. Value of End-of-line resistor is 1K ohms (‘41~0).
4. Entry Delays cannot exceed 60 seconds for UL Commercial Burglary
Listings.
5. Bell timeout cannot be less than 16 minutes for UL Commercial Burglary
Listings.
6. If 4190WH Dual Point RPM are used, tamper detection in Field Address
‘24 must be enabled (enter 0).
7. Field ‘16 Confirmation of Arming Ding must be enabled.
6. field ‘16 AC Loss Alarm after 4 hours must be enabled.