SECTION 10
Testing the System
••••••••••••••••••••••••••••••••••••••••••••••••
Battery Test
When AC power is present, the VISTA-128FBP/VISTA-
250FBP runs a brief battery test every 60 seconds to
determine if there is a battery connected, and runs an
extended battery test every 4 hours to check on the
battery’s condition.
If the VISTA-128FBP/VISTA-250FBP finds that the
battery voltage is low (less than approximately 11.5V),
it initiates a keypad “SYSTEM LOBAT” display and a
rapid keypad beeping sound. It also sends a Low
Battery report to the central station (if programmed).
The keypad is cleared by entering any security code +
OFF, and a Restore report is sent to the central station
if the situation has been corrected.
Dialer Test
The VISTA-128FBP/VISTA-250FBP may be
programmed to automatically transmit test reports to a
central station at intervals ranging from once per hour
to once per 9999 hours (field 27).
Commercial Fire Alarms and Commercial Burglary
requires the test report to be transmitted at least once
every 24 hours. The system can be programmed to send
the first report at any time of the day, or on any day of
the week (field 83).
Fire Drill Test (Code + [#] + 69)
This test causes fire Notification Appliance Circuits to
be activated for the purpose of conducting a fire drill or
bell test. This test can only be activated by the installer
or master users from partition 1 keypads by entering
the corresponding security code + [#] + 69. The burglary
portion of the system must be disarmed.
Keypads display “FIRE DRILL ACTIVE” while the test
is active. The test is stopped by entering any user code
+ OFF.
The system continues to monitor all 24-hour type zones
(fire, panic, etc.) and ends the test if any of these zone
types produce an alarm condition.
This test should be conducted at periodic intervals, as
determined by the local authority having jurisdiction.
One-Man Fire Walk-Test (Code + [#] + 68)
This test causes the system to sound console beeps and
Notification Appliance Circuit dings in response to fire
zone faults (zone type 9, 16 and 17) for the purpose of
allowing proper zone operation to be checked without
triggering alarms. Note that the system will not be
operational as an alarm system (i.e., cannot sense
alarms) while this test is active. The test can only be
activated by the installer by entering the Installer’s
Code and pressing [#] + 68 while the burglary portion of
the system is disarmed.
This test should be conducted at periodic intervals, as
determined by the local authority having jurisdiction.
When testing non-latchin
g
devices, such as heat
detectors, be sure to keep the device faulted
until the system responds with the keypad beep
or siren sound. If the device is faulted only
momentaril
y
, the s
y
stem ma
y
not respond to the
fault.
When this test is first activated, the system will display:
PROMPT
EXPLANATION
USE BELL DING?
0=NO 1=YES
Enter 1 (YES) to have the fire Notification Appliance Circuits associated with each point sound for 3 seconds
when a point is faulted.
Enter 0 (NO) if only keypad sounders are desired.
The next prompt will be displayed.