– 14 –
2*20 ENABLE J7 TRIGGERS by PARTITION [1]
0=disable for displayed partition; 1=enable for displayed
partition
2*22 DISPLAY FIRE ALARMS OF [0]
OTHER PARTITIONS
0=No; 1=Yes
2*23 DISPLAY BURG/PANIC ALARMS OF OTHER [0]
PARTITIONS
10=No; 1=Yes
2*24 DISPLAY TROUBLES OF OTHER [0]
PARTITIONS
0=No; 1=Yes
4th Page Fields
3*57 BELL 2 & AUX. RELAY CONFIRM
ARM. DING 1=enable; [0=disable] Bell 2 Relay
Must be "1" for UL.
3*59 ENABLE BELL 2 & AUX. RELAY
CHIME ANNUNCIATION Bell 2 Relay
1=enable; [0=disable]
3*60 BELL 2 & AUX. RELAY TIMEOUT | |
00-15 times 2 minutes; 00=no timeout [00,00] Bell 2 Relay
Minimum 16 min. for UL Burglary installations.
SUMMARY OF PROGRAMMING COMMANDS
To enter program mode, enter installer code +
[8] + [0] + [0]
To set standard defaults, press *97
To set communication defaults, press *94 +
one of the following: *80=low speed; *81=Ademco
Express; *82=Ademco High Speed; *83=Ademco's
Contact ID
To change to next page of program fields,
press *94
To return to previous set of fields, press *99
To erase account & phone number field
entries, press [*] + field number + [*]
To assign zone descriptors, press #93 +
follow menu prompts
To add custom words, press #93 + follow menu
prompts
To enter Installer's Message, press #93 +
follow menu prompts
To exit program mode, press *99 OR *98: *99
allows re-access to programming mode by installer
code. *98 prevents re-access to programming
mode by installer code.